STEP 7: CONFIGURING UNITS
Prism 2 Technical Guide
23
Configuring Units
Select <Setpoints> to view each setpoint screen associated with
the control type. You must have a Level 3 passcode to access most
of the setpoints on these screens.
Select
<Trendlogs> to open the normal trend log screen and
perform whatever task you normally would from that screen.
Select <Print> to send the printout to a preview window where you
can then select the printer. The printout will be in text format with
a list of the important status information.
Select <Cancel Force Modes> to immediately cancel all force
modes. Force Modes will automatically cancel on their own 10
minutes after Prism 2 goes Off Line.
Controller Override, Schedule, and Holiday
Con guration
At the top of the status screen next to the Occupied/Unoccupied
indicator are the buttons < Override>, < Schedule>, < Holidays>,
and <ALARM>.
The <Override> button overrides the current occupied/unoccupied
operating mode. The <Schedule> button accesses the weekly
schedule and the <Holiday> button accesses the holiday schedule.
The <ALARM> button accesses the Unit Alarm Status &
Con guration Screen, discussed on page 27.
Controller Overrides
If the controller supports it, you can override the
schedule mode of operations by clicking on the
<Override> button. The Overrides Window will
appear.
You can choose
Force Schedule
ON or Force Schedule OFF or
you can choose Fan Only Mode
to force the Main Fan to operate
without any cooling or heating
being activated due to space
temperature demands.
A scheduled force override will
remain in effect until cancelled.
To cancel an override, select the
Auto Scheduling option.
NOTE: Not all units support the Fan Only Mode. In
these cases, it will not be displayed as an option.
Controller Weekly Time Schedules
When you select the <Schedule> button, the
Schedules Window will appear.
The Schedules Window in the example shows an 8:00 AM to 5:00
PM operating schedule for Monday through Friday. The bars on
the right side of the screen give a visual indication of the selected
time periods.
NOTE: Some controllers do not have two start/stop events per
day. The Schedules Window will re ect this by having the Event
#2 columns grayed out.
When you enter a time in any eld, you must designate AM or PM
and press <ENTER>.
NOTE: You MUST press <ENTER> to have the system accept
your entry. If you do not press <ENTER>, the bar graph to the
right will either not display or will not change.
The holiday start and stop times will override the standard
operating hours. The holidays themselves are scheduled in the
Holiday Schedule Window described on page 24.
To eliminate a schedule from any event, simply type a zero and
press <ENTER> for the Start and Stop time for that day. The screen
will display 12:00 AM for both the Start and Stop times, indicating
that the equipment will not activate for that day.
If you want the controller to run the full 24 hours, type a zero and
press <ENTER> to set 12:00 AM for the Start time and type 11:59
PM and press <ENTER> for the Stop time. This ensures the full 24-
hour period will remain in the occupied mode without interruption.
Select < Save> to save your schedule. Select < Restore> to restore
a previously saved schedule. Select < Copy to All> to copy the
schedule to all like controllers, and select < Erase Schedules> to
completely erase the schedule appearing in the window.