1ed_J_^U3_^db_\CicdU]c
Form: AZ-CVC-DS-01A-599-0101
Page
1
of
1
Technical Data CV-C Controller
Power 24 Volt AC Weight 1.5 lb.
Power Consumption 12 VA Maximum Network Connection RS-485
Operating Temp
10
°
F to 149
°
F
Protocol HSI Open Protocol Token Passin
Operating Humidity 90% RH Non-Condensin
Communications RS-485 - 9600 Baud
Inputs: Outputs:
Quantity Available Types Quantity Available Types
T
pe III-10kohm Sensor
Binary
0-10 VDC Sensor
0-5 VDC Sensor
5 Onboard Rela
s
2 Amp @ 24 VAC
N.O. Contacts with Suppressors
4-20mA Sensor
Analog
6
Binar
Contact Closure
1 Modular Phone Jack For
Optional Airflow or SP Sensor
2 0-10 Volt DC Out
WattMaster reserves the right to change specifications without notice
One Year Warranty
Relay Outputs
Only Relay Output #1 (Fan On/Off Only) has a specific function
that cannot be changed. All other outputs are user configurable
in one of the following modes:
•
0
- Not Used (Nothing connected to this output )
•
1
- Heating Stage
•
2
- Cooling Stage
•
3
- Humidifier Enable
•
4
- De-Humidifier Enable
•
5
- Scheduled Relay from Internal Schedule
•
6
- Scheduled Relay from External Schedule (Only 1
Available!)
There are a total of 12 relays that can be configured. Four are
found on the Controller itself (R2 - R5) and the remaining eight
(R6 - R13) are found on the Optional Relay Expansion Board that
can be connected to the PJ2 expansion input.
Mounting
The CV-C Controller is provided with an integral backplate for
mounting inside of a control enclosure. An optional factory control
enclosure for the CV-C Controller is available.
Analog Outputs
There are two Analog Outputs available on this
controller. They are both user configurable as follows:
•
0
- Not Used (Nothing connected to this
output)
•
1
- Economizer (Requires either Supply Air or
Mixed Air Sensor)
•
2
- Relief Fan VFD Signal (Requires Relief
Pressure Sensor)
•
3
- Chilled Water Valve (Requires Supply
Sensor)
•
4
- Hot Water Valve (Requires Supply Sensor)
•
5
- Humidification/De-Humidification
(Requires Humidity Sensor)
Description
The CV-C Controller is a configurable controller that
allows for user configurable inputs and outputs. CV-C
Controllers also have provisions for mounting a Relay
Expansion Board to provide additional heating or cooling
staging capability.
Analog Inputs
Only Analog Input #1 (Space Temp Sensor Only) and
Analog Input #6 (Airflow Sensor Only) have a specific
function that cannot be changed. All other inputs are user
configurable in one of the following modes:
•
0
- Not Used ( Nothing connected to this input )
•
1
- Slide Offset (Requires Flush Mount Wall
Sensor with this Option)
•
2
- Supply Air Temperature
•
3
- Return Air Temperature
•
4
- Mixed Air Temperature
•
5
- Outdoor Air Temperature (Will broadcast to
ALL other controllers)
•
6
- Humidity Sensor (4-20 ma scaling)
•
7
- Humidity Sensor (0-5 VDC scaling)
•
8
- CO² Sensor (4-20 ma scaling)
•
9
- CO² Sensor (0-5 VDC scaling)
•
10
- Relief Pressure Sensor (Requires 0-5 VDC
±0.3" WG Sensor)
•
11
- Dirty Filter Contact (Normally Open)
•
12
- Alarm Contact (Normally Open)
•
13
- Alarm Contact (Normally Closed)
•
14
- Fan Status Contact (Normally Open)
3F33_^db_\\Ub